hubei
Hubei energy storage system fire extinguishing nozzle
There are many fire sprinklers used in energy storage. At present, the local energy storage fire protection system in Hubei mainly involves cabin-level protection, cluster-level protection and package-level protection. Fire sprinklers are designed for these three levels of protection. What are the energy storage fire sprinklers in Hubei? There are mainly cabin-level fire sprinklers, cluster-level fire sprinklers, and package-level fire sprinklers. Fire sprinklers designed for cabin-level protection include cabinet-type perfluorohexanone fire-extinguishing sprinklers and hanging perfluorohexanone fire-extinguishing sprinklers, which can effectively prevent and control energy storage fires.
![]()
1. Energy storage cabin level fire sprinklers
Energy storage cabin-level fire sprinklers are mainly fire sprinklers designed for the relatively closed characteristics of energy storage containers, using cabinet-type or pump-type automatic fire-extinguishing devices, full spray, and submerged fire-extinguishing solutions.
1. Nozzles for cabinet-type perfluorohexanone fire extinguishing devices
Cabinet-type perfluorohexanone fire extinguishing devices generally consist of cabinets, cylinder groups, control valves, nozzles and other components. The cabinet-type perfluorohexanone fire extinguishing device is a prefabricated, fully submerged fire extinguishing, independent complete set, movable fire extinguishing equipment. It has flexible and convenient installation, beautiful appearance, small pressure loss in the fire extinguishing agent delivery pipeline, and high fire extinguishing efficiency. The following is a general selection table of sprinkler heads for cabinet-type perfluorohexanone fire extinguishing devices:
Specifications and models
Flow coefficient
work pressure
Connection thread
Material
QPT120/4.2
120
4.2 MPa
Rp1 1/4
6061/HPb59/304
QPT140/4.2
140
4.2 MPa
Rp1 1/4
6061/HPb59/304
QPT160/4.2
160
4.2 MPa
Rp1 1/2
6061/HPb59/304
QPT180/4.2
180
4.2 MPa
Rp1 1/2
6061/HPb59/304
QPT200/4.2
200
4.2 MPa
Rp2
6061/HPb59/304
QPT220/4.2
220
4.2 MPa
Rp2
6061/HPb59/304
QPT240/4.2
240
4.2 MPa
Rp2
6061/HPb59/304
2. Nozzles for pump-type perfluorohexanone fire extinguishing devices
The pump unit type perfluorohexanone fire extinguishing device is mainly composed of an energy storage pump unit, a control unit and a spray device. It has functions such as automatic detection, automatic identification, and automatic spraying. It can quickly extinguish the fire source in the early stages of a fire and effectively prevent the spread of the fire.
3. Nozzles for hanging perfluorohexanone fire extinguishing devices
Suspended, small-capacity fire extinguishing devices are pre-assembled storage containers, container valves, sprinklers, etc. into independent, hangable gas fire extinguishing devices. This device has the characteristics of flexible layout, fast fire extinguishing speed, high safety factor and stable operation. The nozzle is used to spray the fire extinguishing agent evenly into the protective area to fully cover it and achieve the fire extinguishing effect. The following is a general selection table of sprinkler heads for suspended perfluorohexanone fire extinguishing devices:
Specifications and models
Flow coefficient
work pressure
Connection thread
Material
Closed nozzle operating temperature
QPT2/4.2
2
4.2 MPa
R1/2
304
57℃/68℃
QPT5/4.2
5
4.2 MPa
R1/2
304
57℃/68℃
QPT7/4.2
7
4.2 MPa
R1/2
304
57℃/68℃
QPT10/4.2
10
4.2 MPa
R1/2
304
57℃/68℃
QPT15/4.2
15
4.2 MPa
R3/4
304
57℃/68℃
QPT20/4.2
20
4.2 MPa
R3/4
304
57℃/68℃
QPT30/4.2
30
4.2 MPa
R3/4
304
57℃/68℃
QPT40/4.2
40
4.2 MPa
R1
304
57℃/68℃
QPT50/4.2
50
4.2 MPa
R1
304
57℃/68℃
QPT60/4.2
60
4.2 MPa
R1
304
57℃/68℃
Qpt70/4
70
4.2 MPa
R1
304
57℃/68℃
QPT80/4.2
80
4.2 MPa
R1
304
57℃/68℃
2. Energy storage cluster-level fire sprinklers
The cluster-level energy storage fire safety solution adopts prefabricated perfluorohexanone and other fire extinguishing devices, which can set up fixed-point fire extinguishing and only activate the fire extinguishing device in the fire area. There are also many types of cluster-level fire sprinklers, and various models can meet different flow pressure requirements. The following is a general selection table for energy storage cluster-level fire sprinklers:
Specifications and models
Flow coefficient
work pressure
Connection thread
Material
QPT2/4.2
2
4.2 MPa
R1/2
304
QPT5/4.2
5
4.2 MPa
R1/2
304
QPT7/4.2
7
4.2 MPa
R1/2
304
QPT10/4.2
10
4.2 MPa
R1/2
304
3. Energy storage package level fire sprinkler nozzles
The battery box automatic fire extinguishing device consists of an alarm system, perfluorohexanone supply equipment, partition valves, pipelines, nozzles, etc. It can be widely used in energy storage power stations and new energy vehicle battery box fire extinguishing. The nozzle structure and interface form can be customized according to customer requirements, and good atomization effect is confirmed. When the perfluorohexanone fire extinguishing agent cannot extinguish the fire, the nozzle can also be switched to water spray.
Provides hierarchical protection for the interior of the battery PACK box and the energy storage cabinet space, and the protection objects are refined. Fixed-point fire extinguishing can be set up or the fire extinguishing range can be expanded to achieve the goal of preventing the spread of fire and saving resources.
When thermal runaway continues to occur in PACK, the regasification and carbon monoxide concentrations in the PACK reach 300 ppm, and the ambient temperature in the PACK reaches 70°C, the composite detector alarms and transmits the signal to the host. After analysis, the host starts the cylinder solenoid valve, and the composite detector activates the corresponding package-level puncture valve. The fire extinguishing agent is used to cool down and suppress the fire of the thermally out of control PACK through the pipeline.
The following is the energy storage package level fire sprinkler type and general selection table:
Specifications and models
Flow coefficient
work pressure
Connection thread
Material
Closed nozzle operating temperature
QPT1/1.6
1
1.6 MPa
M16*1.5
6061/HPb59/304
57℃/68℃
QPT1.4/1.6
1.4
1.6 MPa
M16*1.5
6061/HPb59/304
57℃/68℃
QPT2/1.6
2
1.6 MPa
M16*1.5
6061/HPb59/304
57℃/68℃
QPT2.5/1.6
2.5
1.6 MPa
M16*1.5
6061/HPb59/304
57℃/68℃
QPT3.0/1.6
3
1.6 MPa
M16*1.5
6061/HPb59/304
57℃/68℃
QPT3.5/1.6
3.5
1.6 MPa
M16*1.5
6061/HPb59/304
57℃/68℃
QPT4.0/1.6
4
1.6 MPa
M16*1.5
6061/HPb59/304
57℃/68℃
4. Fire sprinklers for battery production line
In the lithium battery manufacturing process, short-circuit inspection, formation, volume separation, aging and finished product storage are process links that are prone to fires. Based on the needs of process scenarios, our company has jointly developed various specifications of perfluorohexanone and water system nozzles with customers to protect fire prevention and control during the lithium battery production process.
![]()
5. Hubei energy storage fire sprinkler manufacturer
The energy storage fire protection system is a new type of fire protection system. It mainly consists of energy storage device, control device, fire extinguishing agent storage device and spray device. Among them, the fire sprinkler head is one of the important components of the spray device. There are many local manufacturers of energy storage fire sprinklers in Hubei. You can investigate from various sources and choose a more powerful manufacturer. In the field of lithium-ion battery fire extinguishing systems, Lanzhong Electromechanical has cooperated with customers to develop various nozzles and nozzles for perfluorohexanone fire extinguishing agents. The products have been widely used in the field of energy storage firefighting.
Lanzhong Mechanical and Electrical has established in-depth cooperative R&D relationships with well-known domestic universities, fire protection research institutes, and leading fire protection companies. It has participated in the preparation of relevant standards and monographs on domestic water mist fire extinguishing technology and perfluorohexanone fire extinguishing technology. It also has extensive cooperation with fire protection companies in the United Kingdom, Sweden, Russia, Morocco, South Africa, India, Malaysia, Australia, Peru and other countries.
Hubei energy storage fire sprinkler manufacturer address:
Wuhan City, Huangshi City, Xiangyang City, Jingzhou City, Yichang City, Shiyan City, Xiaogan City, Jingmen City, Ezhou City, Huanggang City, Xianning City, Suizhou City
Energy storage fire sprinkler is a kind of safety equipment specially used for energy storage systems. Its main function is to quickly start and spray fire extinguishing agent when a fire or other emergency occurs, effectively control the fire, and protect the safety of the energy storage system and its surrounding facilities. The role of energy storage fire sprinklers in energy storage systems cannot be ignored. They can not only prevent the occurrence of fires, but also minimize the damage caused by fires to energy storage equipment and confirm the stability and stability of the energy storage system.
Energy storage fire sprinkler related information:
Energy storage system fire sprinkler nozzle classification
Perfluorohexanone fire sprinkler for energy storage cabinet
Energy storage battery pack fire extinguishing nozzle
Anhui Lanzhong Mechanical and Electrical Equipment Co., Ltd.
WhatsApp: +86-138-6598-5643
![]()
Contact person: Alex Wang
Email: alexwang@watermist.com.cn
Address: Room 101-Room 401, Building B8, Gongtou Lingang New Industrial Park, No.21 Science Avenue, Shou County, Huainan city, Anhui Province, China